Monitoring, recycling, and regeneration: Synecom’s integrated strategy to manage SF₆ across the entire lifecycle of electrical assets.
The energy transition is driving a paradigm shift in the power sector, particularly in the management of fluorinated gases. Although sulfur hexafluoride (SF₆) is destined to be replaced in new high- and extra-high-voltage applications by lower-impact alternatives, the gas will not disappear overnight.
Today, an estimated 514,000 tons of SF₆ remain in global power infrastructure. This installed base will continue operating for decades and cannot be ignored.
Stemming from this realization, Synecom presented its paper, “SF₆ Monitoring, Recycling and Regeneration: Circular Solutions for the Energy Sector,” at the CIGRE Paris Session 2026.
Beyond Simple Phase-Out: From Attendance to Technical Contribution
At CIGRE 2026, Synecom went beyond exhibiting to deliver a key technical contribution to the global debate:
- Poster Session (August 26): Domenico Margheriti, Eng., Head of Synecom SF₆ Division, presented the paper and engaged with leading industry delegates.
- Grand Amphithéâtre (August 27): During the debate on Question 2.02, Synecom addressed a crucial question: Why continue monitoring SF₆ if it is slated for phase-out?
The answer from the paper shifts the traditional perspective: the future of SF₆ lies not solely in replacement, but in the integrated management of its full lifecycle.
Why “Replace” Alone Is Not Enough
SF₆ possesses unique properties (high dielectric strength, chemical stability, excellent arc-quenching capability) that make it almost irreplaceable in existing installations. However, with a GWP of 24,300 and an atmospheric lifetime of roughly 3,200 years, tolerance for leakages is zero.
Today’s challenge is twofold: driving the adoption of new technologies while simultaneously eliminating emissions from gas currently in use.
The industry must shift from the linear model (Use → Vent/Dispose) to a new circular paradigm (Monitor → Recycle → Regenerate).
The Three Pillars of the Synecom Circular Model
1. Monitoring: From Measurement to Predictive Decisions Circular management begins with asset intelligence. Continuous monitoring of key parameters (dew point, pressure, temperature, and density) enables early leak detection and fault prevention.
Unlike simple pressure checks, analyzing temperature-compensated gas density allows operators to:
- Accurately evaluate SF₆ mass stability
- Estimate the leakage rate
- Schedule maintenance interventions before reaching alarm thresholds
2. In-Service Recycling & Purification: Preserving Without Plant Shutdowns Not all degraded gas requires replacement. When monitoring detects moisture or particulate contamination, the paper proposes gas dialysis.
This closed-loop process extracts the gas, filters and dehumidifies it, and reinjects it directly into the compartment.
- The Advantage: The operation occurs while equipment remains energized, eliminating plant downtime, reducing gas handling, and zeroing waste generation.
3. Regeneration: From Waste to High-Purity Resource When gas recovered during decommissioning or major maintenance exhibits high contamination, regeneration takes over via a 4-phase process:
- Recovery & Initial Assessment: Gas recovery and preliminary analysis.
- Pre-treatment & Filtering: Primary treatment and macro-pollutant separation.
- Cryogenic Separation: Selective condensation cryogenic separation.
- Final Purification & Quality Verification: Cavitation micro-pumping, thermal control, and laminar filtration to restore original purity.
Through this processing chain, spent gas ceases to be waste destined for disposal and becomes a reusable resource.
An Integrated Strategy for Industry Sustainability
The value of Synecom’s approach lies in unifying these tools into a single management ecosystem. The phase-out of SF₆ and the maintenance of the installed base are distinct processes that will coexist for decades. Embracing circular management reduces virgin gas consumption, lowers operating costs, and eliminates environmental impact.
The vision presented at CIGRE Paris Session 2026 rests on one principle: every gram of SF₆ must be monitored, preserved, recovered, regenerated, and re-entered into the cycle.